Heading | 01/29/2025 | NOTICE OF COMMENCE | LUCY GUILIANO | APPROVED | 1.29.25 | |
|
Heading | 03/13/2025 | BC ENVR REV | LUCY GUILIANO | APPROVED | 000451128 | |
|
Heading | 03/19/2025 | PRE CONSTR MEETING | LUCY GUILIANO | APPROVED | | |
|
Heading | 04/22/2025 | FRAMING | GREGORY HAMILTON | APPROVED W EXCEPTION | LG | 4/21/2025 11:58:22 AM
SHAKIR
754-221-8633
4/22/2025 7:36:11 AM
9-11
4/22/2025 10:48:16 AM
See approved plans sheet A-8 for locations- locations are highlighted in yellow
|
|
Heading | 05/09/2025 | FRAMING | RONALD DAWKINS | APPROVED W EXCEPTION | eTRAKiT Inspection Request | 5/8/2025 1:07:58 PM
5/8/2025 1:07 PM Marta Herrera
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: marta@whadesign.com
5/9/2025 11:29:31 AM
** FBC 110.9.1 NOT READY
1) Continuing inspection?
2) Southwest portion of wall okay
3) Columns okay for drywall along areas previously approved by Electrical at rear of building.
4) Installed drywall at Electric and MC Utility area
|
|
Heading | 05/14/2025 | DRYWALL | VLADIMIR MELO | APPROVED | eTRAKiT Inspection Request | 5/13/2025 11:58:50 AM
5/13/2025 11:58 AM Marta Herrera
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: marta@whadesign.com
5/14/2025 7:22:09 AM
8-10
5/14/2025 12:33:59 PM
Ok for rear side of construction as well as columns except in the front sw entrance area and mop room in the back across from main entrance (maintenance room, inside of bathrooms). All other areas ok. Check system to unlock insulation so contractor may call it in. See note page e-112 of plans onsite.
|
|
Heading | 05/19/2025 | INSULATION | VLADIMIR MELO | APPROVED | eTRAKiT Inspection Request | 5/16/2025 9:25:37 AM
5/16/2025 9:25 AM Marta Herrera
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: marta@whadesign.com
|
|
Heading | 06/05/2025 | FRAMING | JOSH BELL | APPROVED | eTRAKiT Inspection Request | 6/4/2025 8:17:55 AM
6/4/2025 8:17 AM Marta Herrera
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: marta@whadesign.com
|
|
Heading | 06/25/2025 | FIRE SUB PERMIT REQ | BRUNO MATOS | APPROVED | | 9/17/2024 11:35:42 AM
fire sprinkler sub
|
|
Heading | 07/14/2025 | CEILING GRID | JOSH BELL | APPROVED | eTRAKiT Inspection Request | 7/11/2025 1:08:54 PM
7/11/2025 1:08 PM Marta Herrera
Please call contact person before leaving job site
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: shakirg@oakconstruction.com
|
|
Heading | 07/18/2025 | FINAL STRUCTURAL** | JOSH BELL | CANCELLED | eTRAKiT Inspection Request | 7/17/2025 5:59:06 PM
7/17/2025 5:59 PM Marta Herrera
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: shakirg@oakconstruction.com
7/18/2025 7:57:29 AM
Need prior inspections
|
|
Heading | 07/18/2025 | STRUCTURAL MISC | JOSH BELL | CANCELLED | eTRAKiT Inspection Request | 7/17/2025 5:55:45 PM
7/17/2025 5:55 PM Marta Herrera
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: Shakirg@oakconstruction.com
|
|
Heading | 07/22/2025 | SPECIAL INSP C OF C | JOHN HELLER | APPROVED | | 7/22/2025 8:42:46 AM
see SI report welds, poured cells
|
|
Heading | 07/31/2025 | STRUCTURAL MISC | JOSH BELL | APPROVED | eTRAKiT Inspection Request | 7/30/2025 2:29:52 PM
7/30/2025 2:29 PM Marta Herrera
Please call contact person before leaving job site
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7862730414
e-Mail: shakirg@oakconstruction.com
7/31/2025 10:08:08 AM
Shoe rack inspection approved "in front of house"
|
|
Heading | 08/07/2025 | FINAL FIRE | BRUNO MATOS | CANCELLED | eTRAKiT Inspection Request | 8/6/2025 4:38:29 PM
8/6/2025 4:38 PM Marta Herrera
Please call contact person before leaving job site
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: shakirg@oakconstruction.com
8/7/2025 7:14:34 AM
You still have open sub-permits.
|
|
Heading | 08/14/2025 | FINAL FIRE | FIRE BUCKET | CANCELLED | PER LICI CHANGED TO TCO | 8/13/2025 2:30:21 PM
8/6/2025 4:38 PM Marta Herrera
Please call contact person before leaving job site
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: shakirg@oakconstruction.com
8/6/2025 4:38:29 PM
|
|
Heading | 08/14/2025 | FIRE SUB PERMIT REQ | ALICIA MERRITT | APPROVED | | 9/17/2024 11:35:54 AM
fire alarm sub
|
|
Heading | 08/14/2025 | TCO FIRE | ALICIA MERRITT | DISAPPROVED | STOCKING ONLY | 8/14/2025 11:10:11 AM
1. KEYS NEEDED FOR KNOX BOX AND TO INCLUDEA KEY FOR THE PADLOCK FOR ROOF HATCH
2. WHITE #'S NEEDED FOR ALL BACK DOORS
3. ELECRICAL ROOM SIGNAGE NEEDS TO SAY "NO STORAGE" (INSIDE THE STORE)
4. CEILING TILES PUT BACK IN POLAXCE THROUGHOUT THE BACK ROOM SPACE
5.EXTINGUISHER SIGNAGE NEEDS TO BE VISIBLE FROM THE FRONT OF THE STORE
6. SMALL SQUARE OF DRYWALL IS MISSING IN THE ELCRTICAL ROOM AND NEEDS TO BE FILLED IN APPROPRIATELY
CAPTAIN LICI MERRITT
AMERRITT@CORALSPRINGS.GOV
|
|
Heading | 08/14/2025 | TCO FIRE | ALICIA MERRITT | ACCEPTED | OVERTIME INSPECTION | 8/14/2025 11:06:35 AM
ANY TIME AFTER 4:00
Lance Murphey
Senior Project Manager
954-583-9625 (O)
954-651-8355 (C)
|
|
Heading | 08/14/2025 | TCO STRUCTURAL | JOSH BELL | APPROVED | 1:00 - STOCKING ONLY | |
|
Heading | 08/14/2025 | TCO ZONING | LOGAN ALIA | APPROVED | STOCKING ONLY | 8/14/2025 12:01:08 PM
**Stock and train TCO approved.
|
|
Heading | 08/15/2025 | TCO ELECTRICAL | ARMANDO MEDIAVILLA | APPROVED | FOR STOCKING ONLY | 8/15/2025 7:07:56 AM
8:30-10:30 am
8/15/2025 9:29:18 AM
Electrical TCO Approved stoking only .Tested all Emergency lights all safety at time of the inspection
|
|
Heading | 08/15/2025 | TCO MECHANICAL | FREDERICK STOEGER | APPROVED | STOCKING ONLY | 8/15/2025 7:05:28 AM
10:00-12:00
|
|
Heading | 08/18/2025 | FINAL ZONING | LOGAN ALIA | DISAPPROVED | eTRAKiT Inspection Request | 12/26/2024 8:28:43 AM
**Note-All exterior painting, stucco, or concrete repairs must be textured and painted to match existing at the time of Zonings inspection.
8/15/2025 5:31:11 PM
8/15/2025 5:31 PM Marta Herrera
Please call contact before leaving job site
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: shakirg@oakconstruction.com
8/18/2025 2:41:45 PM
**Inspection disapproved.
**CORRECTIVE ACTIONS:
***Please complete all stucco work around the front doors and paint the ceilings and stucco around the front doors to match the surrounding walls.
***Please remove all construction debris from the back of the building prior to reinspection.
**DESCRIPTION OF ISSUES:
***There is exposed and unfinished stucco on the walls around the front doors. There is mismatched paint on the ceiling above the new front doors.
***There are dumpsters and construction debris at the back of the building that must be removed prior to the final zoning inspection.
|
|
Heading | 09/03/2025 | FINAL FIRE | BRUNO MATOS | DISAPPROVED | eTRAKiT Inspection Request | 9/2/2025 9:41:16 AM
9/2/2025 9:41 AM Marta Herrera
Please call contact number before leaving the job site.
Contact Name: Shakir Gordon
Site Address: 4631 UNIVERSITY DR
Phone: 7542218633
e-Mail: shakirg@oakcinstruction.com
9/3/2025 3:13:43 PM
Checked all the fire extinguishers, exit, and emergency lights.
Need to fix the direction arrow for exit sign "middle" of the store
Storage needs to be moved, aisles, and the exit doors cannot be blocked.
|
|
Heading | | ELC SUB PERMIT REQ | MICHAEL EGEZEINO | APPROVED | | 5/8/2025 2:35:00 PM
1) COMMERCIAL ELECTRIC - slab conduit, wall rough, ceiling rough, electric rough, panel, final **** RECEIVED ***
2) LOW VOLTAGE DATA **RECEIVED**
3) LOW VOLTAGE CAMERAS **RECEIVED**
4) LOW VOLTAGE SECURITY INTRUSION DETECTION
5) LOW VOLTAGE SECURITY -( EAS) ELECTRONIC ARTICLE SURVEILANCE ** RECEIVED**
6) LOW VOLTAGE SOUND, COMMUNICATION ** RECEIVED**
7) LOW VOLTAGE ACCESS CONTROL
8) LOW VOLTAGE WIRELESS ACCESS POINT SYSTEM ( WIFI)
9) SIGNS
6/3/2025 4:17:03 PM
EAS system applied for
|
|
Heading | | FINAL BC ENVR REV | BLDG ADMIN STAFF | | | |
|
Heading | | FINAL FIRE | FIRE BUCKET | | | |
|
Heading | | MCH SUB PERMIT REQ | MECHANICAL PLAN REVIEW | APPROVED | | 9/16/2024 4:16:51 PM
RGH AC
RGH EXH FAN
SD TEST MECH /FIRE
T&B
MECH FINAL
|
|
Heading | | PLB SUB PERMIT REQ | PLUMBING PLAN REVIEW | APPROVED | | 9/16/2024 8:35:43 AM
rough top out final
|
|
Heading | | FINAL STRUCTURAL** | STRUCTURAL BUCKET | | | |
|
Heading | | FINAL ZONING | ZONING BUCKET | | | |
|